Eaton 9SX11Ki
|
General Characteristics
|
|
Topology
|
On-line double conversion with PFC (Power Factor Correction) system |
Configuration
|
Rack/Tower |
Part Number
|
9SX11Ki |
Rating (VA/Watts)
|
11000/10000 |
Dimensions (H x W x D, mm)
|
440 x 260 x 700 |
Weight (kg)
|
86 |
Warranty
|
2 years |
|
|
Electrical Input
|
Connection
|
Hardwired - see manual for terminal block layout |
Input Voltage Range
|
176-276V without derating (up to 100–276V with derating) |
Nominal Voltage
|
200/208/220/230/240/250V |
Frequency
|
50/60 Hz autoselection |
Frequency Range
|
40-70 Hz |
Short Circuit Current
|
150 А |
THDI тока
|
< 5% |
|
|
Electrical Output
|
Voltages
|
200/208/220/230/240/250V +/– 1% |
Voltage THD
|
< 2%
|
Output Receptacles
|
Hardwired |
Overload Capacity
|
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
|
Efficiency (Normal Mode)
|
Up to 95% in Online mode, 98% in Hi-Efficiency mode
|
Output Frequency
|
50/60 Hz autoselect, frequency converter as standard
|
Load Crest Factor
|
3:1
|
|
|
Battery
|
Battery Management
|
ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
Extended Battery Capability
|
EBM |
|
|
Communications
|
User Interface
|
Multilingual graphical LCD display |
Communication Ports
|
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off
|
Communications Slot
|
1 slot for Network-MS card, ModBus-MS or Relay-MS cards
|
|
|
Environmental & Standards
|
Audible Noise
|
<50 dB |
Operating Temperature
|
0 to 40°C continuous |
Safety markings
|
IEC/EN 62040-1, UL 1778, CSA 22.2 |
EMC Markings
|
IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance) |
Approvals
|
CE, CB report (TUV), UL |
|
|
We recommend you to consult with our specialists and they will help you to choose the best configuration and provide information about possible discounts.
|
|
|