Eaton 9PX11KiRTNBP31
|
General Characteristics
|
|
Topology
|
On-line double conversion with PFC (Power Factor Correction) system
|
Configuration
|
Rack/Tower
|
Part Number
|
9PX11KiRTNBP31
|
Rating (VA/Watts)
|
11000/10000
|
Dimensions (H x W x D, mm)
|
440 x 260 x 700
|
Weight (kg)
|
88
|
Warranty
|
2 years
|
Rack Kit Included
|
Yes
|
Contents
(Ships with the following items)
|
9PX Power module
9PX Battery module
External Maintenance Bypass
Network Management Card
2 brackets for 19’ mounting
2 universal rails
Eaton Intelligent Power Software CD
USB Cable
Serial Cable
1 battery cable with comms for automatic battery cabinet recognition
2 supports for tower mounting
link plate for tower mounting
Safety guide
10-language user manual
|
|
|
Electrical Input
|
Connection
|
Hardwired - see manual for terminal block layout
|
Input Voltage Range
|
305V-480V without derating (up to 175V-480V with derating)
|
Nominal Voltage
|
380/400/415V
|
Frequency
|
50/60 Hz autoselection
|
Frequency Range
|
40-70 Hz
|
Short Circuit Current
|
15 A
|
THDI
|
<5%
|
|
|
Electrical Output
|
Voltages
|
200/208/220/230/240/250V +/– 1%
|
Voltage THD
|
< 2%
|
Output Receptacles
|
(4) IEC-320-C19
|
Hardwired - see manual for terminal block layout
|
|
Overload Capacity
|
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
|
Efficiency (Normal Mode)
|
Up to 95% in Online mode, 98% in Hi-Efficiency mode
|
Output Frequency
|
50/60 Hz autoselect, frequency converter as standard
|
|
|
Battery
|
Battery Management
|
ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
|
Extended Battery Capability
|
EBM (3U)
|
|
|
Communications
|
User Interface
|
Multilingual graphical LCD display
|
Communication Ports
|
1 Network management card, 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation
|
|
|
Environmental & Standards
|
Audible Noise
|
<50dB
|
Operating Temperature
|
0 to 40°C continuous
|
Safety markings
|
IEC/EN 62040-1
|
EMC Markings
|
IEC/EN 62040 -2 , IEC/EN 62040-3 (Performance)
|
Approvals
|
CE, CB report (TUV)
|
|
|
We recommend you to consult with our specialists and they will help you to choose the best configuration and provide information about possible discounts.
|
|
|