Eaton 9PX11KiRTNBP31

  General Characteristics
Topology   On-line double conversion with PFC (Power Factor Correction) system
Configuration Rack/Tower
Part Number 9PX11KiRTNBP31
Rating (VA/Watts) 11000/10000
Dimensions (H x W x D, mm) 440 x 260 x 700
Weight (kg) 88
Warranty 2 years
Rack Kit Included Yes
Contents
   (Ships with the following items)
  9PX Power module
  9PX Battery module
  External Maintenance Bypass
  Network Management Card
  2 brackets for 19’ mounting
  2 universal rails
  Eaton Intelligent Power Software CD
  USB Cable
  Serial Cable
  1 battery cable with comms for automatic battery cabinet recognition
  2 supports for tower mounting
  link plate for tower mounting
  Safety guide
  10-language user manual

  Electrical Input
Connection Hardwired - see manual for terminal block layout
Input Voltage Range 305V-480V without derating (up to 175V-480V with derating)
Nominal Voltage 380/400/415V
Frequency 50/60 Hz autoselection
Frequency Range 40-70 Hz
Short Circuit Current 15 A
THDI <5%

  Electrical Output
Voltages 200/208/220/230/240/250V +/– 1%
Voltage THD < 2%
Output Receptacles
   (4) IEC-320-C19
   
   Hardwired - see manual for terminal block layout
   
Overload Capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
Efficiency (Normal Mode) Up to 95% in Online mode, 98% in Hi-Efficiency mode
Output Frequency 50/60 Hz autoselect, frequency converter as standard

  Battery
Battery Management ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
Extended Battery Capability EBM (3U)

  Communications
User Interface Multilingual graphical LCD display
Communication Ports 1 Network management card, 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation

  Environmental & Standards
Audible Noise <50dB
Operating Temperature 0 to 40°C continuous
Safety markings IEC/EN 62040-1
EMC Markings IEC/EN 62040 -2 , IEC/EN 62040-3 (Performance)
Approvals CE, CB report (TUV)