General Characteristics and Price
|
 |
Topology
|
Double-conversion |
|
Configuration
|
Tower/Rackmount |
|
Part Number
|
103006721-6591 |
|
Color
|
Black |
|
Rating (VA/Watts)
|
5000/3500 |
|
Diagnostics
|
Full system self-test |
|
Efficiency
|
>97% in high-efficiency mode; 91% in normal mode; 86% on battery |
|
UPS Bypass
|
Automatic bypass |
|
Dimensions (H x W x D, mm)
|
130 x 444 x 741 |
|
Weight (kg)
|
57 |
|
Rail Kit Included
|
Yes |
|
|
|
Electrical Input
|
|
Connection
|
Hardwired - see manual for terminal block layout |
|
Input Cord
|
Hardwired |
|
Input Voltage Range
|
156–280 Vac (output PF 0.7) |
|
Nominal Voltage
|
230V (220V-240V user selectable) |
|
Frequency
|
50/60 Hz autoselect |
|
Frequency Range
|
40–70 Hz |
|
Breaker Ratings
|
35A |
|
Power Draw of UPS
|
21.7A @230V |
|
|
|
Electrical Output
|
|
Output Receptacles
|
(8) C13, (2) C19, Hardwired |
| On Utility Voltage Regulation
|
±2% of nominal
|
| Frequency Regulation
|
±3 Hz online
|
| Load Crest Factor
|
3:1
|
|
|
|
Battery
|
|
Battery Type
|
5.5 Ah. Sealed, lead-acid; maintenance free |
| Battery Replacement
|
Hot-swappable internal and external batteries
|
| Extended Battery Capability
|
Up to four per 9135, rail kits included for rack mounting
|
| Start On Battery
|
Allows start of UPS without utility input
|
| Recharge Time
|
Six (6) hours to recover 90 percent of nominal backup time after 100 percent RCD load discharge
|
|
|
|
Communications
|
|
User Interface
|
Graphical LCD with blue backlight and text in English, French, German, Portuguese, Italian and Spanish |
|
LEDs
|
Four status-indicating LEDs
|
|
Communication Ports
|
RS-232 standard, RS-232 cable provided
|
|
Relay Output
|
DB-9 Dry Contact-common alarm standard
|
|
Communications Slot
|
Optional communication slot (Mini X-Slot)
|
|
Communications Card Slots
|
Optional: ConnectUPS-MS Card with ModBus RTU interface Serial Management Card-MS for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems
|
|
Power Management Software
|
LanSafe UPS monitoring and management software
|
|
|
|
Environmental & Standards
|
|
Heat Dissipation (BTU)
|
Normal: 1150, Battery: 1650, High Efficiency: 370 |
|
Audible Noise
|
Max 46 dB |
|
Operating Temperature
|
0°C — +40°C |
|
Safety markings
|
CE, GS |
|
EMC Markings
|
IEC/EN 62 040-2 class A |
|
Storage Temperature
|
-20°C to +40°C with batteries and -25°C to +55°C without batteries |
|
Relative Humidity
|
5–90% non-condensing |
|
|
|